VAV B 40 Series
Induction Type
Type: Rectangular / Round
Construction: Galvanized Steel (GI) / Stainless Steel
Application: Light & Medium Duty
Induction VAV Model GB-41 is pressure-independent VAV where air volume control terminals are designed particularly for systems with high variations in heat load. The terminals induce room air and mix it with conditioned primary air, maintaining a nearly constant air volume to the room thus providing sufficient air movement necessary to maintain occupant comfort even in extreme load variations ensuring cold air ‘dumping’ will not occur and comfort zone will be maintained under extremely low primary air temperatures, without producing excessive differences between the supply and the room air temperature.
Data
Technical Features:
- Volume control range from 100 to 10% is possible to the
conditioned zone. - Accurate airflow sensing with 2 X 12 points averaging.
- Low Leakage i.e. less than 2% of V nominal at 750 Pa.
- Designed to produce low NC levels with minimal
pressure drop to the system. - Suitable for low temperature primary systems.
- Air volume capacity upto 2800 CFM
- Suitable for use as constant volume application
- Electronics control factory supply & mounted.
Variety of control options available, based on
applications. - Electronic thermostat & actuator provide accurate
mounting control. - Metal encapsulated edges limit fiberglass insulation
erosion into the airstream. - Single-point power connection reduces installed cost.
- Maintenance free.
Standard Construction
Casing
0.9 mm thick galvanized sheet steel.
Insulation
13 mm thick 32 kg/m³ density Acoustic liner.
Blade
0.9 mm thick galvanized sheet steel.
Flow grid
Flow grid multi point with 12 inlet holes in four concentric
circles.
Axle Shaft
12 mm diameter damper shaft made of galvanized steel.
Bearing
12 mm diameter Brass bearings.
Gasket
Neoprene Gasket.
Controls :
Modulating
Optional Fittings
Controls
Backnet DDC with suitable thermostat.
Duct Heater
Slip-in type electric duct heater (230V AC 1 Phase or
400V AC 3 Phase)
Double skin
Insulated internal walls surface with Galvanized perforated
sheet used for low noise applications to minimise breakout
noise.
Neck connections
Round inlet with round outlet and square inlet with square
outlet.